Free Technician & Contractor Reference

Generator Specs & Maintenance Schedule Lookup

Instant factory oil capacities, valve lash clearances, spark plug gaps, and maintenance cadences for top commercial and residential generators.

Generac14 kW - 26 kW· Liquid Propane / Natural Gas

Guardian Series (Air-Cooled)

Engine: G-Force 800 / 999cc V-Twin OHV (816cc - 999cc)

Engine Oil

5W-30 Full Synthetic

Capacity: 1.9 Quarts

Spark Plugs

0.020 in (0.5 mm)

Champion RC12YC / Generac 0G0767A

Valve Lash (Cold)

Intake: 0.002 - 0.004 in (cold)

Exhaust: 0.002 - 0.004 in (cold)

Battery Size

Group 26R

Min 525 CCA

Factory Maintenance Intervals

Break-In (25 Hours)

Initial Oil & Filter Change

Drain factory break-in oil, install new filter, inspect for oil leaks.

Every 100 Hours / 1 Year

Annual Preventive Maintenance

Replace 5W-30 synthetic oil & filter, replace air filter, check battery float voltage (13.5V-13.8V).

Every 200 Hours / 2 Years

Major Tune-Up & Valve Lash

Replace spark plugs (gap 0.020"), adjust valve lash clearances to 0.002-0.004", test exercise cycle.

Generac15 kW - 50 kW· Diesel

Protector Series (Liquid-Cooled Diesel)

Engine: Inline 4-Cylinder Turbo Diesel (2.4L - 3.4L)

Engine Oil

15W-40 CK-4 Heavy Duty Diesel

Capacity: 6.5 Quarts

Spark Plugs

Compression Ignition (Diesel)

N/A

Valve Lash (Cold)

Intake: 0.008 in (cold)

Exhaust: 0.012 in (cold)

Battery Size

Group 24 / Group 31

Min 650 CCA

Factory Maintenance Intervals

Break-In (50 Hours)

Initial Oil & Fuel Filter Service

Drain engine oil, replace primary fuel filter & water separator.

Every 100 Hours / 1 Year

Oil, Filters & Coolant Check

Change 15W-40 oil, fuel filters, inspect belts and 50/50 ethylene glycol coolant.

Every 2 Years

Coolant Flush & Battery Replacement

Flush cooling system, pressure test radiator cap, test block heater operation.

Kohler14 kW - 26 kW· Liquid Propane / Natural Gas

RCA / RESV Series (Air-Cooled)

Engine: Kohler Command PRO CH740 / CH1000 (725cc - 999cc)

Engine Oil

5W-30 Full Synthetic

Capacity: 2 Quarts

Spark Plugs

0.030 in (0.76 mm)

Champion XC12YC / Kohler 25 132 12-S

Valve Lash (Cold)

Intake: Hydraulic lifters (zero lash check)

Exhaust: Hydraulic lifters (zero lash check)

Battery Size

Group 26R / Group 51R

Min 500 CCA

Factory Maintenance Intervals

Break-In (20 Hours)

Initial Oil Change

Replace oil and filter, inspect fuel connections with sniffer/bubbles.

Every 100 Hours / 1 Year

Annual Service

Change engine oil, oil filter, air filter, inspect battery charger output.

Every 300 Hours / 2 Years

Ignition & Electrical Service

Replace spark plugs (gap 0.030"), clean slip rings, test ATS emergency transfer.

Cummins22 kW - 40 kW· Liquid Propane / Natural Gas

QuietConnect Series (Liquid-Cooled Gas)

Engine: QSG2.4 / QSJ2.4 L4 Gaseous (2.4L Inline 4)

Engine Oil

5W-30 Full Synthetic (Low Ash)

Capacity: 4.5 Quarts

Spark Plugs

0.028 in (0.71 mm)

Denso / Cummins OEM

Valve Lash (Cold)

Intake: 0.010 in (cold)

Exhaust: 0.012 in (cold)

Battery Size

Group 26 / Group 34

Min 575 CCA

Factory Maintenance Intervals

Break-In (50 Hours)

First Oil Change

Drain break-in oil, install Cummins oil filter, retorque clamps.

Every 150 Hours / 1 Year

Annual PM Service

Engine oil, filter, air filter, fuel gas regulator pressure check.

Every 2 Years / 300 Hours

Valves, Plugs & Cooling System

Adjust valve lash, replace spark plugs, flush coolant, test load transfer under building load.

Caterpillar60 kW - 250 kW· Diesel

DE / C-Series Commercial Diesel

Engine: Cat C4.4 / C7.1 ACERT Diesel (4.4L - 7.1L Turbocharged Aftercooled)

Engine Oil

Cat DEO-ULS 15W-40

Capacity: 11 Quarts

Spark Plugs

Compression Ignition (Diesel)

N/A

Valve Lash (Cold)

Intake: 0.010 in (0.25 mm)

Exhaust: 0.020 in (0.50 mm)

Battery Size

Group 31 (24V System - 2 Batteries in Series)

Min 950 CCA

Factory Maintenance Intervals

Monthly (NFPA 110)

30-Minute Operational Run

Run under building load >=30% nameplate, log oil pressure, water temp, frequency (60 Hz).

Semi-Annual

Fuel & Battery Analysis

Specific gravity testing, fuel sample water/microbe check, jacket water heater test.

Annual / 250 Hours

Full PM & Load Bank Test

Cat 15W-40 oil change, primary/secondary fuel filters, 2-hour or 4-hour load bank certification.